GenSol Power

GenSol Online UPS

GS 5/6-10KVA Online UPS

Description: GS 5/6-10KVA Online UPS Series

The GS 5/6-10KVA series is a line of high-performance, double-conversion online UPS systems designed to deliver consistent, reliable power protection for sensitive electronic equipment. Ranging from 5/6kVA and 10kVA, this series ensures zero transfer time during power interruptions, making it ideal for IT infrastructure, telecom, medical equipment, and industrial applications.

With advanced DSP control technology, compact design, and high efficiency, the GS series offers superior voltage regulation, battery management, and intelligent monitoring ensuring uninterrupted uptime for your critical operations.

Features:

  • ⦁ High frequency on-line double conversion technology
    ⦁ DSP (Digital Signal Processors) control technology 
    ⦁ Active Power Factor Correction (APFC), input power factor up to 0.99
    ⦁ Output power factor 0.9/1
    ⦁ Wide input voltage range (110 V ~ 300 Vac) and frequency range (40 ~ 70 Hz)
    ⦁ Auto sensing frequency
    ⦁ 50 / 60 Hz frequency conversion
    ⦁ Cold start
    ⦁ Rear ventilation design and variable speed fan
    ⦁ Effective software and hardware protection
    ⦁ Quick and stable charging, 90% capacity restored in 3-6 hours (standard model UPS)
    ⦁ Settable delayed start when power is restored
    ⦁ Advanced battery management (ABM)
    ⦁ Multiple functions settable via LCD
    ⦁ Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)
    ⦁ Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, EPO function, and 12 A charg
  • ⦁ Safety and Environmental standards certification: ROHS, CE

Technical characteristics:

MODELGS/5/6KVAGS/10KVA
Capacity5/6KVA10KVA
INPUT
Rated Voltage200 / 208 / 220 / 230 / 240 Vac
Voltage Range110 ~ 176 Vac (linear derating between 50% and 100% load );
176 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%)"
BY PASS VOLTAGE RANGE 120 ~ 285 VAC
Input PhaseSingle Phase + Neutral + Ground
Frequency40 ~ 70 Hz (auto-sensing) )
Power Factor0.9/ ≥ 0.99
OUTPUT
Voltage200 / 208 / 220 / 230 / 240 Vac (settable via LCD)
Voltage Regulation±1%
Frequency40 ~ 50 Hz or 50 ~ 60 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode)
Output PhaseSingle Phase + Earth
WaveformPure Sine Wave
Crest Factor3:1
Total Harmonic Distortion(THDi)≤ 2% (linear load), ≤ 5% (non-linear load)
Crest factor3:1
Overload Capability105%–110%: Bypass after 10 min
110%–130%: Bypass after 5 min
130%–150%: Bypass after 1 min
150%: Immediate bypass
SYSTEM
EfficiencyBeep/4s
Transfer timeMains mode to battery mode: 0 ms Inverter mode to bypass mode: 4 ms (typical)
ProtectionsShort-circuit, Overload, Over temperature, Battery Discharge Protection, Surge Protection and Fan Testing Protection
CommunicationsRS232 (standard), USB / RS485 / dry contacts / SNMP (optional)
DisplayLCD or LED
StandardsEN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2, IEC 62040-2, IEC 62040-1, IEC 62040-3 (optional)
ENVIRONMENT
Operating temperature0℃ ~ 40℃
Storage temperature(-25, 55)°C (without batteries)
Relative humidity0 ~ 95% (non-condensing)
Altitude≤ 1000 m, derating 1% for each additional 100 m
IP ratingIP 20
Noise level at 1m< 40 dBA ≤ 50 dBA
BATTERY
DC Voltage192 Vdc (192 - 240 Vdc Settable)
Inbuilt battery of Standard Model12 V / 7 Ah 12 V / 7/9 Ah × 16/20
Battery TypeSealed lead acid, maintenance free & LIFE PO4 compatible
Charging current (max.)Standard model: 90% capacity restored in 3-6 hours; Long time model: depend on the capacity of battery